The basic rules to be
followed and various requirements to be
satisfied for masonry construction are specified in
the codes of practice for structural masonry construction.
This portion of the guide is based on the European structural
design codes - EC6 and EC8. Eurocode 6 specifies the rules
and provisions for structural masonry.
Additional provisions to be considered for
masonry construction in earthquake prone areas are
outlined in Eurocode 8. In this portion of the website are given
specifications and recommendations for an improved type of masonry
construction- reinforced masonry. The information aims at
improving plain and confined brick masonry. Non-Engineered Reinforced masonry applied
to low-rise housing is
quite common in many parts of India, Asia and Latin America.
Reinfoced masonry is popular as well for engineered
masonry construction. It is wide spread in North America, Australia and
New Zealand ,UK and some other areas.
However this type of construction requires good
quality control due to the amount of hidden work and use of concrete infill - grout and
isolated reinforcement.The following main points should be covered for
an earthquake resistant construction :
|
|
| Materials for reinforced masonry construction |
| Masonry units |
EC6 gives
specifications regarding the use of following masonry
units:
- Fired clay units
- Fired clay lightweight units
- Calcium silicate units
- Concrete block units
- Lightweight concrete block units
- Autoclaved aerated concrete units
|
| The
properties of masonry units should comply with the
requirements of relevant European standards (EN
771-1-6). Masonry units are classified into the
following types: solid, perforated unit, hollow unit,
cellular unit, horizontally perforated unit- see Figure 1. |
|
|
Figure 1- Types of masonry units (7) |
| Solid
masonry units are either units without recesses or units
with recesses that are filled with mortar during
construction, or units with up to 25% by volume of
vertical holes. Considering the total volume of holes,
volume of any hole, area of any hole, as well as
combined thickness of webs and shells, EC6 provides the
following classification- Table 1: |
| Criteria |
1 |
2a |
2b |
3 |
Volume of holes (% of the gross volume)1 |
<=25 |
>25-45 for clay units, >25-50 for concrete aggregate units |
>45-55 for clay units, >50-60 for concrete aggregate units2 |
<=70 |
Volume of any hole(% of the gross volume) |
<=12.5 |
<=12.5 for clay units, <=25 for concrete aggregate units |
<=12.5 for clay units, <=25 for concrete aggregate units2 |
Limited by (see below) |
Area of any hole |
Limited by volume (see above) |
Limited by volume (see above) |
Limited by volume (see above) |
<=2800mm2 except units with a single hole when the hole should be <=18000mm2 |
Combined thickness (% of the overall width)3 |
>=37.5 |
>=30 |
>=20 |
No requirement |
Notes: 1.
Holes may consist of formed vertical holes through
the unit or frogs or recesses. 2. If there is national
experience, based on tests, that confirms that the
safety of the masonry is not reduced unacceptably
when a higher proportion of holes is incorporated,
the limit of 55% for clay units and 60% for
concrete aggregate units may be increased for
masonry units that are used in the country with
national experience. 3.The combined thickness is the thickness of webs
and shells, measured horizontally across the unit
at right angles to the face of the wall | |
|
Table 1- EC 6 requirements for the grouping of masonry units |
| This classification is employed to
select the corection factor K in cases where the
characteristic compressive strength fk and shear strength
fvk of the masonry are
calculated on the basis of empirical formulae
correlating normalised compressive strength of masonry
units fb and mortar fm. |
EC 8 provides further requirements
for hollow units used for earthquake resistant masonry
construction as listed:
- The units have less than 50% holes(in % of gross volume)
- Minimum thickness of shells is 15mm
- The vertical webs in hollow and cellular units extend over the entire horizontal
length of the unit
|
In the relevant European standards
(EN 771-1-6) are given minimum mean values of
compressive strength of masonry units to be used for
masonry walls:
- Clay units: min fb=2.5 MPa
- Calcium silicate units: min fb=5.0 MPa
- Concrete units: min fb=1.8 MPa
- Autoclaved aerated concrete units: min fb=1.8 MPa
- Manufactured stone units: min fb=15 MPa
|
According to the EC 8, the minimum
normalised compressive strength of masonry unit, normal
to the bed face, is fb=2.5 MPa. In the case of
hollow clay units and concrete block units it is
recommended that the minimum compressive strength is 7.5
MPa, especially for reinforced masonry walls
construction. EC 6 suggests the use of normalised
compressive strength fb
for design. This is the mean value determined by testing
of at least ten equivalent, air dried, 100 mm by 100 mm
specimens cut from the masonry unit. In the case where
the strength is obtained by testing full sized units,
the mean value of strength is multiplied by the shape
factor d,
which takes into account the actual dimensions of the
unit. In case the compressive stength of masonry is
specified as characteristic strength, it should be first
converted to the mean equivalent using a conversion
factor based on the coefficient of variation, and than
multiplied by the shape factor d (Table 2). |
| Shape factor d
for conversion of mean value of unit's strength to normalised value (EC6) |
| Height [mm] |
Least horizontal dimension [mm] |
| 50 |
100 |
150 |
200 |
>250 |
| 50 |
0.85 |
0.75 |
0.70 |
- |
- |
| 65 |
0.95 |
0.85 |
0.75 |
0.70 |
0.65 |
| 100 |
1.15 |
1.00 |
0.90 |
0.80 |
0.75 |
| 150 |
1.30 |
1.20 |
1.10 |
1.00 |
0.95 |
| 200 |
1.45 |
1.35 |
1.25 |
1.15 |
1.10 |
| >250 |
1.55 |
1.45 |
1.35 |
1.25 |
1.15 | |
|
Table 2- Shape factor for
conversion of mean value of unit's strength to
normalised value (4) |
| Mortar |
According to the specification used
in EC 6, several types of mortar can be used for masonry
walls:
- general purpose mortar, used in joints with thickness greater than 3mm and produced with dense aggregate
- thin layer mortar, which is designed for use in masonry with nominal thickness of joints 1-3mm
- lightweight mortar, which is made using perlite, expanded clay, expanded shale etc.
Lightweight mortars typically have a dry hardened density lower than 1500kg/m3.
|
| In Table 3 below are shown
typical composition of prescribed general purpose mortar
mixes and expected mean compressive strength. |
| Mortar type |
Mean compresive strength |
Approximate composition in
parts of volume |
| Cement |
Hydrated lime |
Sand |
| M2 |
2.5 MPa |
1 |
1.25-2.50 |
2.25-3 times cement and lime |
| M5 |
5 MPa |
1 |
0.50-1.25 |
| M10 |
10 MPa |
1 |
0.25-0.50 |
| M20 |
20 MPa |
1 |
0-0.25 | |
|
Table 3- Typical prescribed
composition and strength of general purpose
mortars (39) |
| Mortars to be used in masonry
construction in earthquake regions should comply with EC
8. According to this standard for the construction of
plain and confined masonry, the minimum compressive
strength of mortar fm is
set to 5 MPa. When mortar is to be used for reinforced
masonry the minimum compressive strength is 10 MPa since
the rebars are embedded in mortar. The bond strength is
specified as a function of type of rebar and type of
mortar. The recommended values of characteristic bond
strength fbok are
specified in Table 4 below: |
| Mortar |
M5-M9 |
M10-M14 |
M15-M19 |
M20 |
fbok for plain bars [MPa] |
0.7 |
1.2 |
1.4 |
1.5 |
fbok for high- bond bars [MPa] |
1 |
1.5 |
2.0 |
2.5 | |
|
Table 4- Characteristic anchorage
bond strength of reinforcement in mortar (4) |
| Mechanical properties of mortar are
determined by testing mortar prisms 40x40x160mm
(EN1015-11). The compressive strength of the mortar is
calculated after averaging the strength values of six
specimens. The thickness of bed and head joints is
recommended to be in the range 8-15mm and all head
joints should be fully filled with mortar. |
| Concrete infill |
| In the case of reinforced masonry
construction care should be taken to ensure the
properties of the concrete infill (or grout). According
to specifications provided in EC 6, the maximum
aggregate size should not exceed 10mm where the least
dimension of the void is 50mm and the rebars cover is
between 15 and 25mm. The maximum aggregate size should
not exceed 20mm where the least dimension of the void is
100mm and the rebars cover is more than 25mm. The values
of characteristic compressive strength of the concrete
infill fck and the
values of characteristic shear strength of concrete
infill fcvk are specified in table 5 below: |
Strength class of concrete |
C12/15 |
C16/20 |
C20/25 |
C25/30 or stronger |
| fck [MPa] |
12 |
16 |
20 |
25 |
| fcvk [MPa] |
0.27 |
0.33 |
0.39 |
0.45 | |
|
Table 5 Characteristic compressive fck and
shear strength fcvk of concrete infill (4) |
| Reinforcing steel |
| Steel bars are used as
reinforcement in the case of reinforced masonry (Figure 2). |
|
|
Figure 2- Typical ladder and truss type of prefabricated bed joint reinforcement |
According to EC 6, reinforcing steel
may be assumed to possess adequate elongation ductility,
if the following requirements are satisfied:
- for high dutility class: euk > 5% and (ft/fy)k > 1.08
- for normal dutility class: euk > 2.5% and (ft/fy)k > 1.05,
|
where: e
uk= the characteristic value
of the unit elongation at max tensile stress,
ft=
tensile strength of rebar steel,
fy=
yield strength of rebar steel,
(ft/fy)k = the characteristic value
of ft/fy |
| In the case where high bond rebars
with diameter less than 6mm is used it should not be
considered as having high ductility. When prefabricated
ladder-type or truss-type bed joint reinforcement is
used it should be considered as having normal ducility. |
| Definition of reinforced masonry construction systems |
| To beginning of document |
As
discussed in the Confined masonry document, the confinement of plain masonry walls
greatly improves both the strength and the ductility.
However as research and experience from past
earthquakes have shown that to fully employ the resistance
and energy dissipation capacity of masonry, the plain
masonry has to be reinforced.
A
construction system where steel reinforcement is
embedded in the mortar joints of masonry or placed in
holes and after filled with concrete or grout is called
Reinforced masonry. There are various practices and
techniques to achieve reinforced masonry. According to
the ways in which reinforcement is arranged, reinforced
masonry can be classified into three types:
- Reinforced hollow unit masonry
- Reinforced grouted cavity masonry
- Reinforced pocket type walls
|
| The
most common type is the reinforced hollow unit masonry.
Units from group 2a and 2b are used for this purpose.
This construction type is discussed in the Concrete
block reinforced masonry section. |
The
second type of reinforced masonry walls- the reinforced
grouted cavity masonry is the recognised earthquake
resistant type of masonry. It consists of a cavity
masonry wall constructed from group 1 masonry units.
Into the cavity is placed a steel mesh providing the
vertical and horizontal rebars. In order to achieve
integrity of the wall the two leaves are connected by
means of standard wall ties or rebars. The size and
number of connecting ties are determined according to
design calculations. However at least 4f6 rebar links or an
equivalent wall ties per m2 of wall area should be
provided. After completition of the reinforcement
details the cavity is grouted or infilled with concrete.
The leaves are usually one masonry unit thickness (about
100 mm) and the size of the cavity is 60 to 100 mm wide.
The concreting of the cavity can be done in steps after
construction of each course or in one operation after
the masonry walls in the whole storey have been laid.
Before grouting the cavity, all mortar droppings on
foundations or rebars should be removed from the
previous grout stop to ensure proper bonding. To achieve
satisfactory grouting vent holes should be formed in the
wall to allow for the air to escape and facilitate
removing away mortar debris at the bottom of each grout
stop. The vent holes are formed as work proceeds and
these can be in the form of open mortar joints or
masonry units left out.
Reinforced grouted cavity masonry wall construction is shown on Figure 3.
|
|
|
Figure 3- Reinforced grouted cavity masonry construction |
The
third type of reinforced masonry walls-the reinforced
pocket type walls is common for engineered structural
masonry construction. Vertical wall reinforcement can be
placed in vertical ducts( pockets) formed between solid
or hollow masonry units. This is the case when so called
"quetta bond"( a brick and a half wall thickness bond)
is constructed. In "quetta bond" close spacing of
vertical rebars is possible. The reinforced pocket type
masonry aslo allows for forming reinforced masonry
columns, where ducts of bigger size can accommodate
multiple bars as well as stirrups for concrete infill or
grout confinement.
For this type
of reinforced masonry the vertical rebars are placed
into position ideally before the laying of masonry
units. Horizontal reinforcement is placed in the bed
joints at vertical spacing maximum 600 mm. The vertical
reinforced ducts are filled with concrete or grout as
the costruction of the wall progresses. Proper planning
is necessary to ensure rebar splices lengths, anchoring
lengths, correct cover and keeping the concrete infill
or grout surface of each grout stop clean from mortar
debris. Reinforced pocket cavity masonry wall construction
is shown on Figure 4 |
|
|
Figure 4- Reinforced pocket cavity masonry construction |
| In order to achieve
durability of the reinforced wall it is essential to
ensure rebar protection against corrosion or fire
damage. For this purpose is required that the
reinforcement has sufficient concrete/grout cover. For
unprotected steel in dry, humid or aggressive
environment the cover should be respectively 20 ,25 and
40 mm thick. |
For
all three types of reinforced masonry to be constructed
in seismic regions reinforcement specifications are
provided in EC 8. According to this code the minimum
percentage of horizontal reinforcement, referred to as
the gross area of the section should be min 0.05%. The
min percentage for vertical reinforcement is not
specified, however according to EC 8 are required rebars
with cross-sectional area min 400 mm2 placed at free edges of
walls and at every wall intersection. Reinforced with
rebars zones of the masonry wall should be max 4 m
apart.
Limitation of the size of horizontal rebars is
required to achieve good embedment in the mortar. It is
recommended that rebar diameter is max 6 mm when placed
in standard 10 mm bed joint.
The
effectiveness of the reinforcement however strongly
depends on the type and quality of the masonry ie.
masonry units and mortar. When subject to seismic load
the bond between the rebars and mortar deteriorates.
Consequently high tensile stresses and yielding in
rebars cannot be develop preventing ductile behaviour
and energy dissipation. For certain hollow masonry units
premature crushing of face shells under cyclic lateral
load may occur even in cases where the compressive
strength of the units is good.
In order to achieve a
ductile behaviour of masonry is necessary that the shear
strength of the wall is greater than the bending
strength to ensure bending failure. Therefore increased
amount of vertical reinforcement at the edges of wall
may not improve the resistance of the wall particularly
with weak masonry units. Thus the minimum
percentage of reinforcement, either vertical or
horizontal, depends on the strength of the masonry
units.
The maximum percentage of reinforcement should
also be limited based on the strength of the masonry
units and mortar such that a ductile bending failure is
possible. The requirements for anchoring and lapping of
reinforcement are similar to those specified for
reinforced concrete structures. All reinforcement should
be anchored to allow for the stresses in the bar to
develop. On way to achieve economic anchorage is to
terminate the rebar past the point where it is no longer
required. This is called straight anchorage. According
to EC 8 straight anchorage is not allowed for rebars
with diameter more than 8 mm. Ec 6 provides the
following formulae to calculate the anchorage length
lb: |
| lb = (f/4)*(fyk/cs)*(cM/fbok) |
| where
the meaning of symbols in the above equations are as
follows: |
| f - the diameter
of reinforcing bar, |
| fyk - the characteristic
strength of reinforcing steel, |
| fbok - the characteristic
anchorage bond strength, |
| cs, cM - the partial safety factors |
When
anchorage is achieved by hook ending the anchorage
length for rebars in tension can be reduced by 30%.
Lapping of rebars is necessary to
facilitate construction and progress of the works. The
provision of laps should be considered by the designer.
When lapping bars through staggering care is needed to
avoid rebars congestion which can result in poor
workmanship. The required lap length is determined from
the formulae discussed above. In the equation however the diameter of
the smaller of the two bars participates. Depending on
the detail the lap length provided should be equal to :
- lb for bars in compression
and for bars in tension where less than 30% of the
bars in the section are lapped, and where the clear
distance between the lapped bars in transverse
direction is not less than 10f and the mortar or
concrete cover is not les than 5f.
- 1.4lb for bars in tension where
either 30% or more of the bars at the section are
lapped, or if the clear distance between lapped bars
in transverse direction is less than 10f , or the
mortar or concrete cover is less than 5f.
- 2lb for bars in tension where
both 30% or more of the rebars at the section are
lapped, and the clear distance between the lapped bars
in a transverse direction is less than 10f or the
mortar or concrete cover is less than 5f.
Typical anchorages of reinforcing bars are shown on Figure 5.
|
|
|
Figure 5- Typical anchorages of reinforcing bars (4) |
| Mechanical properties for verification of masonry walls |
| To beginning of document |
| This part of the document explains the mechanical properties of masonry
for verification of masonry walls. This section is included in cases where engineered building is required. |
| Earthquake resistance of masonry walls |
In the event of an earthquake, apart from the existing gravity loads, horizontal racking loads are imposed on walls.
However, the unreinforced masonry behaves as a brittle material. Hence if the stress state within the wall exceeds masonry strength, brittle failure occurs,
followed by possible collapse of the wall and the building. Therefore unreinforced masonry walls are vulnerable to earthquakes,
and should be confined and/or reinforced whenever possible.
Masonry walls resisting in-plane loads usually exhibit the following three modes of failure (see Figure 6):
- Sliding shear- a wall with poor shear strength, loaded predominantly with horizontal forces
can exhibit this failure mechanism. Aspect ratio for such walls is usually 1:1 or less (1:1.5)
- Shear- a wall loaded with significant vertical load as well as horizontal forces can fail in shear.
This is the most common mode of failure. Aspect ratio for such walls is usually about 1:1. Shear failure
can also occur for panels with bigger aspect ratio ie. 2:1, in cases of big vertical load.
- Bending- this type of failure can occur if walls are with improved shear resistance.
For bigger aspect ratios ie. 2:1 bending failure can occur due to small vertical loads, rather than
high shear resistance. In this mode of failure the masonry panel can rock like a rigid body (in cases of low
vertical loads).
|
|
|
Figure 6- Failure modes for masonry walls subject to in-plane loads |
| Lateral resistance and ductility of plain masonry walls can be improved by
reinforcing the masonry with steel. Reinforcing bars can be placed horizontally in the bed joints and embedded with mortar.
Vertical reinforcing bars can be placed in hollow block masonry channels.
The contribution of vertical and horizontal reinforcement to the resistance of the wall, falling in shear, is shown on Figure 7.
The shear strength of such reinforced wall depends on the tension capacity of horizontal steel, dowel action of vertical steel,
arching of masonry and interlocking of crack surfaces. |
|
|
Figure 7- Mechanism of action of vertical and horizontal reinforcement of a masonry wall failing in shear (11) |
| Mechanical properties |
In order to estimate the resistance of masonry walls, the following mechanical properties for
the masonry needs to be determined:
- The compressive strength- f
- The shear strength- fv
- The bending strength- fx
- The stress-strain relationship, s-e
|
Other essential mechanical characteristics of masonry:
- The tensile strength- ft, as an equivalent to shear strength- fv
- The modulus of elasticity- E
- The shear modulus- G
- The ductility factor- m
|
| The ductility factor is determined
only for a specific structural element(specific
proportions, boundary conditions etc). It cannot be
determined for the masonry itself. Mechanical
characteristics of masonry are determined by testing
standard specimens of masonry wallets and walls
according to code EN 1052. |
| Compressive strength |
Compressive strength is
determined by testing masonry specimens of at least 1.5
units length and 3 units height or by testing walls of
1.0-1.8 m length and 2.4-2.7 m height.
In cases where
the masonry specimen is slender(height/thickness>20),
lateral displacements at the mid height of the wall are
measured. The slenderness can be taken into account
using the measured value for this displacement d and the
thickness of the wall t. Thus the measured compressive
strength can be increased by the following factor:
t/(t-d),
provided the increase is not more than 15%.
According to
EN 1052-1 three identical specimens are tested and the
results evaluated. In cases where the measured mean
compressive strength f of masonry is different from the
one of its constituents( masonry units and mortar) by
25% the value of f is modified. The characteristic
compressive strength of masonry fk is determined as the
smaller value of either fk=f/1.2 or fk=fmin.
When verifying load
bearing masonry and test data is not available, the
characteristic compressive strength of plain masonry
made with general purpose mortar may be calculated on
the basis of normalised compressive strength of masonry
units fb and compressive
strength of mortar fm as
follows: |
| fk = K*(fb0.65)*(fm0.25) [MPa], |
and fm is less than 20 MPa
or 2fb, whichever is the
smaller. The value of constant K depends on the
classification of masonry units into groups as per Table 1.
Below are shown recommended values for K:
- 0.60 for group 1 masonry units in a wall without longitudinal mortar joint,
- 0.55 for group 2a masonry units in a wall without longitudinal mortar joint,
- 0.50 for group 2b masonry units in a wall without longitudinal mortar joint, and
for group 1 masonry units in a wall with longitudinal mortar joint,
- 0.45 for group 2a masonry units in a wall with longitudinal mortar joint,
- 0.40 for group 2b masonry units in a wall with longitudinal mortar joint, and
for group 3 masonry units
|
| Shear strength |
| Shear strength of masonry is
defined as a combination of initial shear strength under
zero compressive load and increase in strength due to
compressive stresses perpendicular to the shear plane.
Initial shear strength at zero compressive stress is
denoted with fvko. This
property is determined according to EN 1052-3 by testing
a triplet specimen such that only shear stresses develop
in the mortar to masonry unit contact planes. A minimum
of five triplets are tested. The minimum acceptable
value of fvko is 0.03
MPa. The characteristic shear strength of plain masonry
is then calculated as follows: |
| fvk = fvko+0.4*sd, |
| where sd is the design compressive
stress perpendicular to the shear plane. The value of
sd should be greater than
0.065fb and a limiting
value specified in EC 6 depending on masonry unit's
group and mortar quality. In Table 4, are shown
typical values of initial shear strength at zero
compression fvko and
limiting values of characteristic shear strength fvk . |
Masonry unit group |
Mortar |
fvko [MPa] |
Limiting fvk [MPa] |
1 clay |
M10-M20 |
0.3 |
1.7 |
| M2.5-M9 |
0.2 |
1.5 |
1 other |
M10-M20 |
0.2 |
1.7 |
| M2.5-M9 |
0.15 |
1.5 |
2a clay |
M10-M20 |
0.3 |
1.4 |
| M2.5-M9 |
0.2 |
1.2 |
2a other 2b clay |
M10-M20 |
0.2 |
1.4 |
| M2.5-M9 |
0.15 |
1.2 | |
|
Table 4- Shear strength at zero compression
fvko and limiting values of characteristic shear strength fvk (4) |
Another approach exists for
determining the shear resistance of plain masonry walls,
that lead to virtually same results. According to this approach, the shear failure
of masonry wall, ie. diagonal cracking of the wall, is caused by the principal tensile stresses.
The shear strength can be determined by reducing the masonry wall to a
structural element from elastic, homogeneous and isotropic material, experiencing plane stress
state. For this purpose are evaluated the principal compressive and tensile stresses,
respectively that develop in the middle section of the wall.
Thus the value of the principal tensile stresses, measured when the wall panel is loaded in shear
at failure, defines the tensile strength, ft.
The equations for principal compressive and the principal tensile stresses in
plain masonry wall panel under vertical load- N, and lateral load- H, are : |
| sc = SQRT((so/2)2+(b*t)2)+so/2 , |
| st = SQRT((so/2)2+(b*t)2)-so/2 , |
| And the plane of the principal stresses is defined as follows: |
| fc = ft = 0.5*ARCTAN(2*t/so), |
| where the meaning of symbols in the above equations are as follows: |
| so = N/Aw - average compressive stress due to vertical load N, |
| t = H/Aw - average shear stress due
to lateral load H, |
| Aw - the horizontal cross
section area of the wall, |
| b -
the shear stress distribution factor, depending on the
geometry of the wall and N/Hmax ratio. For a wall with
geometrical aspect ratio height/length=1.5, b=1.5 . |
| Hmax - the maximum resistance
of masonry wall |
| The principal tensile stress that develop in the wall at the
moment of maximum resistance- Hmax is called the tensile
strength of masonry: |
| ft = st = SQRT((so/2)2+(b*tHmax)2)-so/2 , |
In the
above equation ft is the
tensile strength of masonry and tHmax-
the average shear
stress in the wall at the attained maximum resistance
Hmax |
| The
lateral resistance Hs,w
of a plain masonry wall panel, loaded in shear is evaluated by : |
| Hs,w = Aw*(ft/b)*SQRT((so/ft)+1) |
| When
the resistance envelope is bilinear relationship, the
above equation is multiplied by a factor of 0.9. If the
design value of the shear resistance Hsd,w should be correlated
with the design seismic action, in the above equation
take part the characteristic value of tensile strength
and a material partial safety factor : |
| Hsd,w = Aw*(ftk/cM*b)*SQRT((sdcM/ftk)+1) |
There
is currently no standard testing procedure for
evaluating the shear strength fv or tensile strength ft.
One possibility is to use monotonic
diagonal compression test. Another test is subjecting
the wall panel to monotonic or cyclic racking load. The
effect of compressive stresses in the masonry is taken
into account in these tests. Table 5 shows values of
characteristic tensile strength of masonry -ftk correlated with values for
the initial shear strength at zero compressive stress- fvko |
Unit [MPa] |
Group |
Mortar [MPa] |
Strength [MPa] |
| ftk |
fvko |
| 10 |
1 - clay |
0.5 |
0.04 |
0.10 |
| 15 |
1 - clay |
2.5 |
0.18 |
0.20 |
| 7.5 |
2a - clay |
2 |
0.30 |
0.10 |
| 15 |
2a - clay |
2.5 |
0.12 |
0.20 |
| 15 |
2a - clay |
5 |
0.18 |
0.20 |
| 7.5 |
2a - other |
5 |
0.27 |
0.15 |
| 7.5 |
2a - other |
5 |
0.27 |
0.15 |
| 7.5 |
2b - clay |
3 |
0.10 |
0.20 | |
|
Table 5- Correlation between experimental
characteristic tensile strength ftk and initial shear strength
fvk0 of masonry (14) |
| By
analysing test results it has been established that the
ratio between the tensile and compressive strength of
any type of masonry varies in the following margins: |
|
0.03fk <= ftk <= 0.09fk |
| Bending strength |
| In
cases where the masonry needs to be verified for
out-of-plane loads the bending strength is the governing
factor. The bending strength parallel to bed joints (see Figure 9) is
denoteed with fx1 and
the bending strength perpendicular to bed joints (see Figure 8) is
denoted with fx2.
According to EC 6 the value of fx1 should be taken as zero
when evaluating seismic resistance. |
|
|
Figure 8- Vertical orientation of failure plane and corresponding bending strength normal to bed joints |
|
|
Figure 9- Horizontal orientation of failure plane and corresponding bending strength parallel to bed joints |
| Elastic properties |
The
modulus of elasticity E of masonry can be determined
after compression tests. The elastic modulus is defined
as a secant modulus at service load condition. This load
level corresponds to 1/3 of the maximum vertical
load. When determined by testing
E modulus value is not available the following equation
may be used : |
| E=1000fk |
| However in the calculated value of
E modulus may not be correct. Reliable E values are the
one in the margin: |
| 200fk <= E <= 2000fk |
| Theoretically and as specified in
EC 6 the G modulus is evaluated as being 40% of the E
modulus. In reality the values of shear modulus G are
much lower. Reliable G values are the one in the
margin: |
| 1000ftk <= G <= 2700ftk |
| The
discrepancy between experimental and predicted values
for the mechanical properties of masonry can be
explained with the composite nature of the material.
There are wide variety of not only masonry units but
also mortars and various composition of the masonry wall
itself. Therefore the testing of masonry is essential
step in seismic resistance verification of masonry
houses. |
| Planning and layout |
| To beginning of document |
Surveys of
earthquake damaged residential masonry wall houses
and analysis of the causes of damage indicated that, well tied
buildings with
well defined, continuous load path to the foundations
perform much better in earthquakes than building lacking
such features. Well defined, continuous load path can be
achieved with regular structural layout and uniformity
both in plan and elevation. The degree of symmetry is
also found to have a significant influence on earthquake
resistance. Damage can be five to ten times worse in
irregular buildings compared to regular ones.
Thus
satisfactory seismic behaviour can be guaranteed by
following the requirements for regular and uniform
layout both in plan and elevation, interconnectivity
between structural members and strength of materials.
To summarise an earthquake resistant structural form
for masonry wall structure is the one which
is:
- Regular both in plan and
elevation i.e. uniform and symmetrical
- Redundant - capable of
providing adequate resistance even after a failure of
a structural member
- With rigid floors
interconnected with walls that ensure diaphragm action
- Stable foundation
should be provided able to transmit the maximum seismic loads
from the superstructure to the foundation soil
|
Masonry buildings with horizontal
irreguliarities and lack of symmetry may have
considerable eccentricity between the mass centre and
stiffness centre giving rise to damaging coupled
lateral/torsional response. Horizontal irregularities in
the form of extensions, projections etc. may cause
stress concentration and local failures since these
extensions are prone to vibrate separetely from the rest
of the structure. On the other
hand vertical irregularity in masonry building may cause
stress concentration at a horizontal plane that can lead
to total collapse. In order to achieve satisfactory
redundancy at least to lines of load bearing walls are
required in each principal direction of the building.
Lack of rigid floors will prevent proportionate load
transfer onto walls at each floor level as well as will
not provide out of plane restraint. Not supported
masonry walls at floor level tends to separate at
corners and/or fail out of their plane, causing collapse
of floor or roof. |
According to EC 8 the following
general criteria for structural regularity in plan and
elevation should be considered:
- The building structure is
approximately symmetrical along each principal axis in
plan, for both stiffness and mass distribution. A
sufficient number of load bearing walls with
approximately the same stiffness, should be provided
in both principal direction of the building -see Figure 10
|
|
Figure 10- Structural walls distribution in plan |
|
|